Manufacturer’s Declared Parameters
Input / Output Model CC-PAOH01 – High-Level Analog Output with HART

CU-PAOH01 – High-Level Analog Output with HART

IOTA Models CC-TAOX01

CU-TAOX01

Non Redundant 6”
CC-TAOX11

CU-TAOX11

Redundant 12”
Output Type 4-20 mA
Output Channels 16
Output Ripple < 100 mV peak-to-peak at power line frequency, across 250 Ω load
Output Temperature Drift

Output Readback Accuracy

0.005% of Full Scale/°C

±4% of Full Scale

Output Current Linearity ± 0.05% of Full Scale nominal
Resolution

Calibrated Accuracy

± 0.05% of Full Scale

± 0.35% of Full Scale (25oC) including linearity

Directly Settable Output Current Range 0 mA, 2.9 mA to 21.1 mA
Maximum Resistive Load

(24 V supply = 22 VDC through 28 VDC)

800 ohms
Maximum Output Compliant Voltage

(24 V supply = 22 VDC through 28 VDC)

16 V
Maximum Open Circuit Voltage

Response Time

(DAC input code to output)

Gap (0 mA) of Output to Field on Switchover

22 V

settles to within 1% of final value within 80 ms

10 ms maximum (applies to Redundancy only)

The C300 Controller is constructed using the Series C form factor that employs an Input Output Termination Assembly (IOTA) and an electronics module which mounts and connects to the IOTA. One C300 Controller contains all of the control functionality and the communications functions with plug-in modules.
The C300 Controller may operate in both non-redundant and redundant configurations. Redundant operation requires a second identical controller and connecting cables, which is the typical configuration. The C300 Controller is connected to the associated I/O hardware by a pair of I/O Link Interface cables