BROWSE PRODUCTS

HIGH-QUALITY PROCESS CONTROL SOLUTIONS

Home > Transmitters > Yokogawa > EJA series > Yokogawa EJA440A -DD Traditional-mount High Gauge Pressure Transmitter
Yokogawa EJA440A -DD Traditional-mount High Gauge Pressure Transmitter

Yokogawa EJA440A Traditional-mount High Gauge Pressure Transmitter

Yokogawa EJA440A -DD Traditional-mount High Gauge Pressure Transmitter

The high performance gauge pressure transmitter model EJA440A can be used to measure liquid, gas,or steam pressure.

Stability

±0.1 % of URL per 12 months

Power Supply Effects “

±0.005 % per Volt (from 21.6 to 32 V DC, 350 Ω)

Output “◊

Two wire 4 to 20 mA DC output with digital communi

cations. BRAIN or HART FSK protocol are superim

posed on the 4 to 20 mA signal.

Failure Alarm

Output status at CPU failure and hardware error;

Up-scale: 110%, 21.6 mA DC or more(standard)

Down-scale: -5%, 3.2 mA DC or less

-2.5%, 3.6 mA DC or less (Optional

code /F1)

Note: Applicable for Output signal code D and E

Weight

C capsule: 6.8 kg (15 lb) without integral indicator,

mouting bracket, and process connector.

D capsule: 8.0 kg (17.6 lb) without ‚-tegral indicator,

mouting bracket, and process connector.

Yokogawa EJA440A Traditional-mount High Gauge Pressure Transmitter

Yokogawa EJA440A -DD Traditional-mount High Gauge Pressure Transmitter

Description

Ambient Temperature Limits

(approval codes may affect limits)

-40 to 85 ˚C (-40 to 185 ˚F)

-30 to 80 ˚C (-22 to 176 ˚F) with LCD Display

Process Temperature Limits

(approval codes may affect limits)

-40 to 120 ˚C (-40 to 248 ˚F)

Ambient Humidity Limits

5 to 100 % RH @ 40 ˚C (104 ˚F)

Supply Voltage “◊”
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code
/A)
10.5 to 30 V DC for intrinsically safe, Type n,
nonincendive, or non-sparking type
Minimum voltage limited at 16.4 V DC for digital
communications, BRAIN and HART