  • Place of Origin: Japan
  • Brand Name: Yokogawa
  • Model Number: FX1006
  • Product Name: Yokogawa FX1006 Paperless Recorder
  • Safety: good
  • Quality: International Standard for Yokogawa FX1006 Paperless Recorder
  • Accuracy: High Accuracy
  • Model: FX1006

Yokogawa Paperless Recorder

Yokogawa FX1006 Paperless Recorder

 

GENERAL SPECIFICATIONS

Construction

Mounting: Flush panel mounting (on a vertical plane) Mounting may be inclined downward up to 30 degrees from a horizontal plane.
Allowable panel thickness: 2 to 26 mm
Front panel: Water- and dustproof: Complies with IEC529-IP65 (excluding side-by-side mounting)

Input

Number of inputs: FX1002: 2 channels, FX1004: 4 channels, FX1006: 6 channels, FX1008: 8 channels, FX1010: 10 channels, FX1012: 12 channels
Measurement intervals: FX1002, DX1004: 125 ms, 250 ms FX1006, FX1008, FX1010, FX1012: 1 s, 2 s, 5 s
Inputs: DCV (20, 60, 200 mV, 1, 2, 6, 20, 50 V, 1-5 V) TC (R, S, B, K, E, J, T, N, W, L, U, WRe) RTD (Pt100, JPt100) DI (Contact input, TTL level) DCA (with external shunt resistor attached)
Measurement/display accuracy: Standard operating conditions: Temperature: 23 ± 2°C Humidity: 55% ± 10%RH Power supply voltage: 90 to 132 or 180 to 250 VAC Power supply frequency: 50/60 Hz ± 1% Warm-up time: At least 30 minutes. Other ambient conditions such as vibration should not adversely affect the operation.
Input Range Measurement Accuracy Digital Display Max. Resolution
DCV 1-5 V ±(0.05% of rdg+3 digits) 1 mV
Thermocouple* K ±(0.15% of rdg + 0.7°C) –200 to –100°C: ±(0.15% of rdg + 1°C) 0.1°C
RTD Pt100 ±(0.15% of rdg+0.3°C) 0.1°C 0.1°C

* Does not include the accuracy of reference junction compensation

Alarm Function

Number of alarm levels: Up to four for each channel
Alarm types: High limit, low limit, differential high limit, difference low limit, high rate-of-change limit, low rate-of-change limit, alarm delay high limit, and alarm delay low limit

Event Action Function

General: A particular action can be executed by particular event.
Number of event actions: 40 actions can be set
urs when the power is turned on.

Batch Function

General: Data display and data management with batch name, text field function and batch comment function are available.

Power Supply

Rated power supply: 100 to 240 VAC (automatic switching)
Allowable power supply voltage range: 90 to 132 or 180 to 264 VAC
Rated power supply frequency: 50/60 Hz (automatic switching)
Power consumption: Max. 45 VA (for 240 VAC power supply)

NORMAL OPERATING CONDITIONS

Supply voltage: 90 to 132, 180 to 250 VAC
Rated power supply frequency: 50 Hz ±2%, 60 Hz ±2%
Ambient temperature: 0 to 50°C
Ambient humidity: 20 to 80% RH (at 5 to 40°C), 10 to 50% (at 40 to 50°C)