BROWSE PRODUCTS

HIGH-QUALITY PROCESS CONTROL SOLUTIONS

Home > DCS > Yokogawa > Oxygen Analyzer > Yokogawa ZR202G Zirconia oxygen analyzer
  • Place of Origin: Japan
  • Brand Name: Yokogawa
  • Model Number: ZR202G
  • Product Name: Yokogawa ZR202G Zirconia oxygen analyzer
  • Safety: good
  • Quality: International Standard for Yokogawa ZR202G Zirconia oxygen analyzer
  • Accuracy: High Accuracy
  • Model: ZR202G

Yokogawa ZR202G Integrated type Explosion-proof Zirconia Oxygen Analyzer O2 Analyzer

ZR202G Yokogawa O2 Analyzer is EXAxt series ZR Integrated type Zirconia Oxygen/Humidity Analyzer which usually used or combustion monitoring and control in a wide variety of applications and help industries to make considerable achievements in energy saving such as iron and steel, electric power, oil and petrochemical, ceramics, pulp and paper, food, and textiles, also to various combustion facilities, such as incinerators and small- and medium sized boilers. Combustion monitoring and control using the analyzer also contribute to a lowering of CO2, SOx, and NOx emissions by allowing for more complete combustion, thus preventing global warming and air pollution.
ZR202G Yokogawa O2 Analyzer is normally for monitoring the oxygen concentration or achieving low oxygen combustion in large- or small-sized boilers, various industrial furnaces, and combustion equipment.

ZR202G Yokogawa O2 Analyzer owns below typical features:

1. The built-in heater assembly of the probe can be replaced on site, reducing maintenance costs
2. The probe uses a long-life, high-reliability Zirconia sensor
3. Remote maintenance using digital communications(HART) reduces maintenance costs
4. Wide range of wetted part material optional, SUS 316 (JIS), Hastelloy, Inconel
5. Integrate both probe and converter, to reduce wiring, piping, installation costs.
6. Measure either oxygen concentration or humidity
7. Infrared switch operation

ZR202G SPECIFICATION
Measurement object
 Oxygen concentration in combustion exhaust gas and mixed gas
Measurement system
 Zirconia system
Display
6-digit LCD
Switch
Three optical switches
Measurement range
0.01 to 100 vol%O2
Output signal
4 to 20 mA DC, two points (maximum load resistance 550 Ω)
Setting range
Any setting in the range of 0 – 5 vol%O2 to 0 – 100 vol%O2 (in 1 vol%O2), or partial range
Digital communication (HART)
250 to 550 Ω, depending on number of field devices connected to the loop (multi-drop mode)
Sample gas pressure
-5 to +250 kPa
Sample gas temperature
0 to 700℃ (Probe only)
700 to 1400℃ (with 0.15m probe and High Temperature Probe Adapter)
Probe length
0.4, 0.7, 1.0, 1.5, 2.0, 2.5, 3.0 m
Contact output
Four points (one is fail-safe, normally open)
Contact input
Two points
Calibration
Method ; zero/span calibration
Calibration mode ;automatic, semi-automatic and manual (with optical switch)
Construction of detector
Heater and thermocouple replaceable construction.
Non-explosion-proof. Equivalent to NEMA4X/IP66
Converter Construction
Outdoor installation. Equivalent to NEMA4X/IP66
Ambient temperature
 -20 to 55℃
Power supply
 85 to 264 V AC; 45 to 66 Hz