Endress Hauser Electromagnetic Flowmeter Proline Promag 53E

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag 53E offers highest accuracy in the most complex and demanding measuring tasks.

Brand :Endress Hauser
Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 53E
Diameter:DN 15 to 600 (½ to 24″)
Measurement error:Volume flow: ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
Range:4 dm³/min to 9600 m³/h (1 to 44 000 gal/min)
Pressure range: PN 40, Class 150, 20K
Process Temperature:–10 to +110 °C (+14 to +230 °F)
Output: 4 modular outputs:
0‐20 mA (active)/4‐20 mA (active/passive)
Pulse/frequency (passive)
Relay output
Switch output (passive)
Input:2 modular inputs:
Status input
0‐20 mA (aktiv)/4‐20 mA (aktiv/passiv)

Endress Hauser Electromagnetic Flowmeter Proline Promag 53E

Application
• The measuring principle is virtually independent of pressure, density, temperature and viscosity
• Fully suitable for basic applications in the chemical and process industry
Device properties
• Nominal diameter: max. DN 600 (24″)
• Ex approvals for Zone 2
• Liner made of PTFE
• 4-line backlit display with touch control
• Device in compact or remote version
• HART, PROFIBUS DP/PA, Modbus RS485, FF, EtherNet/IP

Your benefits
• Cost-effective sensor – ideal solution for basic requirements
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Quality – software for filling & dosing, density, electrode cleaning and also advanced diagnostics
• Easy calculation – bidirectional totalizers
• Automatic recovery of data for servicing

Endress Hauser Electromagnetic Flowmeter Proline Promag 51W

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag 51W offers highly accurate measurement of liquids for a wide range of standard applications.

Brand :Endress Hauser
Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 51W
Diameter:”DN 25…2000,1″…78″
Measurement error:± 0.5%,± 0.2%
Range:0…110’000 m3/h
Pressure range: PN6…40
Process Temperature:-20…+80℃(176℉)
Output: 4 … 20 mA pulse / frequency, state
Input:Status

Endress Hauser Electromagnetic Flowmeter Proline Promag 51W

Application
Electromagnetic flowmeter for custody transfer with cold water:
• Flow measurement up to 110,000 m3/h
• Fluid temperature (for a certified device) up to +30 °C
• Process pressures up to 40 bar
• Fitting lengths to DVGW/ISO
• PTB approval
• Metrological Classes A and B
• With national type examination for cold water (GER)
• Continous operation at Qmax possible
Application-specific lining materials:
• Polyurethane, hard rubber, PFA and PTFE
Approvals for hazardous area:
• ATEX
Lined measuring pipes with materials approved for drinking water:
• KTW, WRAS, ACS, etc.
Application-specific measurement output:
• With a certified totalizer display and pulse output

Your benefits
Promag measuring devices offer you cost-effective flow measurement with a high degree of accuracy for a wide range of process conditions.
The uniform Proline transmitter concept comprises:
• Modular device and operating concept resulting in a higher degree of efficiency
• Uniform operating concept
The tried-and-tested Promag sensors offer:
• No pressure loss
• Not sensitive to vibrations
• Simple installation and commissioning

Endress Hauser Electromagnetic Flowmeter Proline Promag 51P

Electromagnetic Flowmeter

Electromagnetic Flowmeter Promag 51P Is dedicated for chemical and process applications with corrosive liquids and high medium temperatures.

Brand :Endress Hauser
Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 51P
Diameter:”DN 15…600,1/2″…24″
Measurement error:± 0.5%,± 0.2%
Range:0…9’600 m3/h
Pressure range: PN10…40
Process Temperature:-40…+150℃
Output: 4 … 20 mA pulse / frequency, state
Input:Status

Endress Hauser Electromagnetic Flowmeter Proline Promag 51P

Application
Electromagnetic flowmeter for custody transfer with cold water:
• Flow measurement up to 110,000 m3/h
• Fluid temperature (for a certified device) up to +30 °C
• Process pressures up to 40 bar
• Fitting lengths to DVGW/ISO
• PTB approval
• Metrological Classes A and B
• With national type examination for cold water (GER)
• Continous operation at Qmax possible
Application-specific lining materials:
• Polyurethane, hard rubber, PFA and PTFE
Approvals for hazardous area:
• ATEX
Lined measuring pipes with materials approved for drinking water:
• KTW, WRAS, ACS, etc.
Application-specific measurement output:
• With a certified totalizer display and pulse output

Your benefits
Promag measuring devices offer you cost-effective flow measurement with a high degree of accuracy for a wide range of process conditions.
The uniform Proline transmitter concept comprises:
• Modular device and operating concept resulting in a higher degree of efficiency
• Uniform operating concept
The tried-and-tested Promag sensors offer:
• No pressure loss
• Not sensitive to vibrations
• Simple installation and commissioning

Endress Hauser Electromagnetic Flowmeter Proline Promag 50W

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag 50W offers highly accurate measurement of liquids for a wide range of standard applications.

Brand :Endress Hauser
Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 50W
Diameter:”DN 25…2000,1″…78″
Measurement error:± 0.5%,± 0.2%
Range:0…110’000 m3/h
Pressure range: PN6…40,Cl 150…300,JIS 10…20K,AWWA Class D,AS 2129
Process Temperature:-20…+80℃(176℉)
Output: 4 … 20 mA pulse / frequency, state
Input:Status

Endress Hauser Electromagnetic Flowmeter Proline Promag 50W

Application
Electromagnetic flowmeter for bidirectional measurement of liquids with a minimum
conductivity of 5 μS/cm:
• Drinking water
• Wastewater
• Sewage sludge
• Flow measurement up to 110000 m³/h
(484315 gal/min)
• Fluid temperature up to +80 °C (+176 °F)
• Process pressures up to 40 bar (580 psi)
• Lengths in accordance with DVGW/ISO
Application-specific lining of the measuring pipe from
polyurethane or hard rubber with the following drinking
water permissions:
• KTW
• WRAS
• NSF
• ACS
Approvals for hazardous area:
• ATEX
• IECEx
• FM
• CSA
• NEPSI
Connection to process control system:
• HART
• PROFIBUS DP/PA
• FOUNDATION Fieldbus
• MODBUS RS485

Your benefits
Promag measuring devices offer you cost-effective flow measurement with a high degree of accuracy for a wide range of process conditions.
The uniform Proline transmitter concept comprises:
• Modular device and operating concept resulting in a higher degree of efficiency
• Software options for batching, electrode cleaning and for measuring pulsating flow
• High degree of reliability and measuring stability
• Uniform operating concept
The tried-and-tested Promag sensors offer:
• No pressure loss
• Not sensitive to vibrations
• Simple installation and commissioning

Endress Hauser Electromagnetic Flowmeter Proline Promag 50P

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag 50P offers highly accurate measurement of liquids for a wide range of applications.

  • Brand :Endress Hauser
  • Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 50P
  • Diameter:”DN 15…600,1/2″…24″
  • Measurement error:± 0.5%,± 0.2%
  • Range:0…9’600 m3/h
  • Pressure range: PN10…40,Cl 150…300,JIS 10…20K,AS 2129
  • Process Temperature:-40…+180℃
  • Output: 4 … 20 mA pulse / frequency, state
  • Input:Status

Endress Hauser Electromagnetic Flowmeter Proline Promag 50P

Electromagnetic flowmeter for bidirectional measurement of liquids with a minimum
conductivity of ≥ 5 μS/cm:
• Acid, alkalis
• Paints
• Pastes
• Water, wastewater etc.
• Flow measurement up to 9600 m³/h (42268 gal/min)
• Fluid temperature up to +180 °C (356 °F)
• Process pressures up to 40 bar (580 psi)
• Lengths in accordance with DVGW/ISO
Application-specific lining materials:
• PTFE
• PFA
Approvals for hazardous area:
• ATEX
• IECEx
• FM
• CSA
• NEPSI
• TIIS

Connection to process control system:
• HART
• PROFIBUS DP/PA
• FOUNDATION Fieldbus
• MODBUS RS485
Your benefits
Promag measuring devices offer you cost-effective flow measurement with a high degree of accuracy for a wide range of process conditions.
The uniform Proline transmitter concept comprises:
• Modular device and operating concept resulting in a
higher degree of efficiency
• Software options for batching, electrode cleaning and
for measuring pulsating flow
• High degree of reliability and measuring stability
• Uniform operating concept
The tried-and-tested Promag sensors offer:
• No pressure loss
• Not sensitive to vibrations
• Simple installation and commissioning

Endress Hauser Electromagnetic Flowmeter Proline Promag 50L

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag 50L offers highly accurate measurement of liquids for a wide range of standard applications.

  • Brand :Endress Hauser
  • Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 50L
  • Diameter:Lap joint flange; lap joint flange, stamped plate: DN 25 to 300 (1 to 12″)
    Fixed flange: DN 350 to 2400 (14 to 90″)
  • Measurement error:Volume flow (standard): ±0.5 % o.r. ± 1 mm/s (0.04 in/s)
    Volume flow (option): ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
  • Range:9 dm³/min to 162 000 m³/h (2.5 gal/min to 1030 Mgal/d)
  • Pressure range: PN 16, Class 150
  • Process Temperature:Liner material hard rubber: 0 to +80 °C (+32 to +176 °F)
    Liner material polyurethane: –20 to +50 °C (–4 to +122 °F)
    Liner material PTFE: –20 to +90 °C (–4 to +194 °F)
  • Output: 3 outputs:
    0‐20 mA (active)/4‐20 mA (active/passive)
    Pulse/frequency output (passive)
    Switch output (passive)
  • Input:Status input

Endress Hauser Electromagnetic Flowmeter Proline Promag 50LH

Application
• The measuring principle is virtually independent of pressure, density, temperature and viscosity
• Fully suitable for standard applications in the water and wastewater industry
Device properties
• Up to 30 % less sensor weight
• Nominal diameter: DN 25 to 2400 (1 to 90″)
• Maximum reduced installation length to DVGW/ISO
• 2-line backlit display with push buttons
• Device in compact or remote version
• HART, PROFIBUS PA/DP

Your benefits
• Reduced installation costs – flexible mounting by one-of-akind lap-joint flange concept (DN < 350/14″)
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Fast commissioning – application-specific Quick Setups
• Safe operation – display provides easy readable process information
• Fully industry compliant – IEC/EN/NAMUR

Endress Hauser Electromagnetic Flowmeter Proline Promag 50H

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag 50H offers highly accurate measurement of liquids for a wide range of standard applications.

  • Brand :Endress Hauser
  • Model: Endress Hauser Electromagnetic Flowmeter Proline Promag 50H
  • Diameter:”DN 2…100,1/12″…4″
  • Measurement error:± 0.5%,± 0.2%
  • Range:0…282 m3/h
  • Pressure range: PN16…40
  • Process Temperature: -20…+150℃
  • Output: 4 … 20 mA pulse / frequency, state
  • Input:status

Endress Hauser Electromagnetic Flowmeter Proline Promag 50H

Application
• The measuring principle is virtually independent of pressure, density, temperature and viscosity
• For the smallest flow quantities and demanding hygienic applications
Device properties
• Liner made of PFA
• Sensor housing made of stainless steel (3-A, EHEDG)
• Wetted materials CIP, SIP cleanable
• Device in compact or remote version Promag 53
• 4-line backlit display with touch control
• HART, PROFIBUS PA/DP, Modbus RS485, FF, EtherNet/IP

Your benefits
• Flexible installation concept – numerous hygienic process connections
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts Promag 53
• Quality – software for filling & dosing, density, electrode cleaning and also advanced diagnostics
• Easy calculation – bidirectional totalizers
• Automatic recovery of data for servicing

Endress Hauser Electromagnetic Flowmeter Proline Promag W800

Electromagnetic Flowmeter

Electromagnetic Flowmeter Endress Hauser Proline Promag W800 is the specialized sensor for all applications in the water industry.

  • Brand :Endress Hauser
  • Model: Endress Hauser Electromagnetic Flowmeter Proline Promag W800
  • Diameter:DN 25 to 300 (1 to 12″)
  • Measurement error:Volume flow: ±0.5 % o.r. ± 2 mm/s (±0.5 % o.r. ± 0.08 in/s)
  • Range:15 dm³/min to 2500 m³/h (4 to 11 000 gal/min)
  • Pressure range: PN 40, Class 300, 20K
  • Process Temperature: Liner material hard rubber: 0 to +80 °C (+32 to +176 °F)
    Liner material polyurethane: –20 to +50 °C (–4 to +122 °F)
  • Output: Pulse/switch output (passive)
  • Input:Status input

Endress Hauser Electromagnetic Flowmeter Proline Promag W800

Application
• The electromagnetic measuring principle is unaffected by pressure, temperature and flow profile
• Certified sensor for the most demanding water and wastewater applications
Device properties
• International drinking water approvals
• Degree of protection IP68 (Type 6P enclosure)
• Approved for custody transfer to MI-001/OIML R49
• Transmitter housing made of durable polycarbonate
• All in 1 housing incl. batteries & wireless modem
• Measuring intervals can be adapted individually

Your benefits
• For direct underground installation or permanent underwater use
• Secure, reliable long-term operation – robust and completely welded sensor
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• No power grid required – battery lifetime of up to 15 years
• Worldwide transmission of measured data and events via email and SMS – integrated GSM/GPRS modem
• Reliable data storage – integrated SD card

Endress Hauser Proline Promag W400 Electromagnetic Flowmeter

Electromagnetic Flowmeter

Electromagnetic Flowmeter Promag W400 saves time and costs thanks to the broad functionality of its water- and wastewater-optimized transmitter.

  • Brand :Endress Hauser
  • Model: Endress Hauser Proline Promag W400 Electromagnetic Flowmeter
  • Diameter:DN 25 to 2000 (1 to 78″)
  • Measurement error:Volume flow (standard): ±0.5 % o.r. ± 1 mm/s (0.04 in/s)
    Volume flow (option): ±0.2 % o.r. ± 2 mm/s (0.08 in/s), Flat Spec
  • Range:9 dm³/min to 110 000 m³/h (2.5 gal/min to 700 Mgal/d)
  • Pressure range: PN 40, Class 300, 20K
  • Process Temperature: Liner material hard rubber: 0 to +80 °C (+32 to +176 °F)
    Liner material polyurethane: –20 to +50 °C (–4 to +122 °F)
  • Output: 3 ouputs:
    0‐20 mA/4‐20 mA HART (active)
    Pulse/frequency/switch output (passive)
    Pulse/frequency output (passive)
    Switch output (passive)
  • Input:Status input

Endress Hauser Proline Promag W400 Electromagnetic Flowmeter

Application
• The measuring principle is practically independent of pressure, density, temperature and viscosity
• The specialist for very demanding applications in the water and wastewater industry
Device properties
• International drinking water approvals
• Degree of protection IP68 (Type 6P enclosure)
• Approved for custody transfer to MI‐001/OIML R49
• Transmitter housing made of durable polycarbonate or aluminum
• Same housing concept for compact/remote version
• Integrated data logger for measured values monitoring

Your benefits
• For direct underground installation or permanent underwater use
• Safe, reliable long-term operation – robust and completely welded sensor
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Safe operation – no need to open device thanks to touch ncontrol display, backlighting
• Time‐saving local operation without additional software and hardware – integrated web server
• Integrated verification – Heartbeat Technology™

Endress Hauser Proline Promag P 200 Electromagnetic Flowmeter

Electromagnetic Flowmeter

Electromagnetic Flowmeter Promag P 200 is dedicated for chemical and process applications with corrosive liquids and high medium temperatures.

  • Brand :Endress Hauser
  • Model: Endress Hauser Proline Promag P 200 Electromagnetic Flowmeter
  • Diameter:DN 15 to 200 (½ to 8″)
  • Measurement error:Volume flow: ±0.5 % o.r. ± 2 mm/s (0.08 in/s)
  • Range:4 dm3/min to 1100 m3/h (1 to 4850 gal/min)
  • Pressure range: PN 40, Class 300, 20K
  • Process Temperature: Liner material PFA: –20 to +150 °C (–4 to +302 °F)
    Liner material PTFE: –40 to +130 °C (–40 to +266 °F)
  • Output: 4‐20 mA HART (passive)
    Pulse/frequency/switch output (passive)
  • Input:None

Endress Hauser Proline Promag P 200 Electromagnetic Flowmeter

Application
• The measuring principle is virtually independent of pressure, density, temperature and viscosity
• Dedicated for chemical and process applications with corrosive liquids and high medium temperatures
Device properties
• Nominal diameter: max. DN 200 (8″)
• All common Ex approvals
• Liner made of PTFE or PFA
• Loop-powered technology
• Robust two-chamber housing
• Plant safety: worldwide approvals (SIL, Haz. area)

Your benefits
• Versatile applications – wide variety of wetted materials
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Convenient device wiring – separate connection compartment
• Safe operation – no need to open the device due to display with touch control, background lighting
• Integrated verification – Heartbeat Technology™

Endress Hauser Proline Promag P 100 Electromagnetic Flowmeter

Electromagnetic Flowmeter

Electromagnetic Flowmeter Promag P 100 is dedicated for chemical and process applications with corrosive liquids and high medium temperatures.

  • Brand :Endress Hauser
  • Model: Endress Hauser Proline Promag P 100 Electromagnetic Flowmeter
  • Diameter:DN 15 to 600 (½ to 24″)
  • Measurement error:Volume flow (standard): ±0.5 % o.r.± 1 mm/s (0.04 in/s)
    Volume flow (option): ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
  • Range:4 dm³/min to 9600 m³/h (1 to 44 000 gal/min)
  • Pressure range: PN 40, Class 300, 20K
  • Process Temperature: Liner material PFA: –20 to +150 °C (–4 to +302 °F)
    Liner material PFA high‐temperature: –20 to +180 °C (–4 to +356 °F)
    Liner material PTFE: –40 to +130 °C (–40 to +266 °F)
  • Output: 4‐20 mA HART (active)
    Pulse/frequency/switch output (passive)
  • Input:None

Endress Hauser Proline Promag P 100 Electromagnetic Flowmeter

Application
• The measuring principle is virtually independent of pressure, density, temperature and viscosity
• Dedicated for chemical and process applications with corrosive liquids and high medium temperatures
Device properties
• Nominal diameter: max. DN 600 (24″)
• All common Ex approvals
• Liner made of PTFE or PFA
• Robust, ultra-compact transmitter housing
• Local display available

Your benefits
• Versatile applications – wide variety of wetted materials
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Space‐saving transmitter – full functionality on smallest footprint
• Time‐saving local operation without additional software and hardware – integrated web server
• Integrated verification – Heartbeat Technology™

Endress Hauser Proline Promag L400 Electromagnetic Flowmeter

  • Brand :Endress Hauser
  • Model:Endress Hauser Proline Promag L400 Electromagnetic Flowmeter
  • Diameter:Lap joint flange, lap joint flange, stamped plate: DN 25 to 300 (1 to 12″)
    Fixed flange: DN 350 to 2400 (14 to 90″)
  • Measurement error:Volume flow (standard): ±0.5 % o.r. ± 1 mm/s (0.04 in/s)
    Volume flow (option): ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
  • Range:9 dm³/min to 162 000 m³/h (2.5 gal/min to 1030 Mgal/d)
  • Pressure range: PN 16, Class 150
  • Process Temperature: Liner material hard rubber: 0 to +80 °C (+32 to +176 °F)
    Liner material polyurethane: –20 to +50 °C (–4 to +122 °F)
    Liner material PTFE: –20 to +90 °C (–4 to +194 °F)F)
  • Output: 3 ouputs:
    0‐20 mA/4‐20 mA HART (active)
    Pulse/frequency/switch output (passive)
    Pulse/frequency output (passive)
    Switch output (passive)
  • Input:Status input

Endress Hauser Proline Promag L400 Electromagnetic Flowmeter

Application
• The measuring principle is practically independent of pressure, density, temperature and viscosity
• Perfectly suitable for standard applications in the water and wastewater industry
Device properties
• Up to 30 % less sensor weight
• Nominal diameter: DN 25 to 2400 (1 to 90″)
• Maximum reduced installation length to DVGW/ISO
• Transmitter housing made of durable polycarbonate or aluminum
• Same housing concept for compact/remote version
• Integrated data logger for measured values monitoring

Your benefits
• Reduced installation costs – flexible mounting by one‐of‐akind lap‐joint flange concept (DN < 350/14″)
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Safe operation – no need to open the device due to display with touch control, background lighting
• Time‐saving local operation without additional software and hardware – integrated web server
• Integrated verification – Heartbeat Technology™